Heptafluoropropane Fire Extinguishing System in Dual Cabinets


Release time:

2026-10-29

Heptafluoropropane Fire Extinguishing System in Dual Cabinets

Jiangxi Fengrui Fire Protection Technology Co., Ltd. is a fire protection enterprise based in Xinyu Economic Development Zone, Yushui District, Xinyu City, Jiangxi Province, China. The dual-cabinet Heptafluoropropane fire extinguishing system is part of its heptafluoropropane series. It is a standalone, total flooding system with one or more pipeless units for each protected area.

The system consists of fire detectors, an automatic alarm control panel, a fire suppression control unit and the fire suppression equipment. The cabinet design keeps the agent cylinders, valves and control parts in one unit. The system is intended for rooms that need a clean agent without water damage.

The dual-cabinet range covers models GQQ40x2/2.5-ZY, GQQ70x2/2.5-ZY, GQQ90x2/2.5-ZY, GQQ100x2/2.5-ZY, GQQ120x2/2.5-ZY, GQQ150x2/2.5-ZY and GQQ180x2/2.5-ZY. External dimensions run from 980 x 450 x 1200 mm to 980 x 500 x 2100 mm. Agent weight ranges from 0 to 89.6 kg up to 0 to 403 kg, and protected volume from about 116 cubic meters to about 524 cubic meters.

The design effectiveness is about 0.6 to 0.8 kg per cubic meter. Operating ambient temperature is 0 to 50 degrees Celsius, and the storage pressure is 2.5 MPa. The system can start automatically or manually, and the start and feedback circuits are connected in parallel.

When selecting a Heptafluoropropane fire extinguishing system, buyers should confirm the room volume, the enclosure tightness, the required agent concentration, the model and the cylinder location. It is also useful to confirm the detector type, the control panel, the alarm devices and the wiring plan. The protected volume figures in the table give a starting point for the model choice.

Jiangxi Fengrui Fire Protection Technology Co., Ltd. is located in Xinyu Economic Development Zone, Yushui District, Xinyu City, Jiangxi Province, China. Contact Mr. Yu at 18879057119, Mr. Shu at 19870016119 or Mr. Xiao at 13320005905, or send an email to 13879002373@163.com. Send the room volume and project requirement, and the team can confirm the Heptafluoropropane fire extinguishing system and the next steps.